Chapter 21: Relay & Electronic Interlocking

                                     Section 1: Design Criteria of Signalling Circuits


                 21.1.1  Circuits - General
                         (a) The Detailed designs for circuits of interlocking may be required for;


                            (i)  Route Setting Type i.e. on the basis of Entry/Exit principle.
                            (ii)  Non-route Setting Type  i.e. Route is set  with  individual operation  of
                                 points for existing installations or alterations.

                         (b) The designs shall be suitable for RE as per stipulations in Chapter 22 of
                             SEM on "Requirements of signalling in 25 KV AC electrified areas".
                         (c)  The designs shall be in accordance with the approved signalling plans,
                             Control Table, Control Panel diagram, Relay contact analysis and relay
                             rack arrangements.

                         (d) The  designs  shall  be  suitable  for  the  specific  type  equipment  to  be
                             installed such as Make of Electronic Interlocking (Distributed or Central),
                             MSDAC, SSDAC, UFSBI,Block Working built into Electronic Interlocking
                             etc and the type of Interfacing & features, they provide. Use of dual OFC
                             in Distributed type of Electronic Interlocking, are desirable as they reduce
                             extent of copper cables & provide an alternate path in case of Failures.

                         (e) The  drawings  &  designs  shall  be  made  in  accordance  with  Typical
                             templates,  RDSO`s  Standard  circuits/templates,  guidelines,  Board
                             guidelines, Industry`s best practices & principles of Reliability, Availability,
                             Maintenance & Safety in mind.

                 21.1.2  Control Panels - General

                         (a) The display of the layout on the front of the Control Panel referred to as the
                             illuminated diagram shall be well proportioned. Where additional facilities are
                             likely to be provided, domino type panel shall, preferably be used. The areas
                             covered by each track circuit shall be clearly distinguished by use of different
                             colours.

                         (b) The operating members, namely route switches/buttons, point switches etc.,
                             referred  to  in  the  following  clauses  shall  normally  be  provided  on  the
                             illuminated  diagram  itself  in  Geographical  order.  A  separate  illuminated
                             diagram for indication and a separate 'console' containing all the operating
                             members may also be provided.


                         (c) At  Non-route  setting  type  installations,  the  route  may  be  set  with
                             individual operation of points.


                         (d) The  Route  setting  shall  be  on  "Entry/Exit"  principle  for  installations  of
                             Route Setting type. Each route shall be controlled by means of two push
                             buttons - one at the entrance and the other at the exit of the route.