Section 11: Earthing for Outdoor Signalling Equipment

               19.11.1  Types of Earths

                        (a) Earths are of two types


                            (i)  Functional  Earth:  The  earth  return  used  for  block  instruments  is  a
                                functional  earth  which  is  used  to  conduct  the  current  through  earth
                                during normal operation/function of equipment.

                            (ii) Protective  Earth:  This  earth  for  dissipating  surges,  which  comes  in
                                contact with equipment’s connections through Surge Protection Devices
                                (SPD) during Lightning or surges so as to protect the equipment.

                        (b) Perimeter  Ring  Earth  (PRE)  shall  be  provided  around  building  housing
                            signalling equipment. Chasis of all S&T equipment shall be bonded to BRC
                            (Bonding Ring Conductor) provided inside the Power Equipment Room or
                            Signal Equipment Room. BRC is to be connected to MEEB in Power room
                            and from there to PRE as per extant guidelines. In case, no BRC exists,
                            chassis of the equipment shall be connected directly to MEEB (Main Equi-
                            potential Earth Busbar).

                        (c) Earthing  shall  be  provided  as  per  approved  specifications,  drawings  and
                            code of practice issued by RDSO.


                        (d) The  maximum  earth  resistance  shall  be  specified  as  per  OEM  &  RDSO
                            recommendations.


               19.11.2  Purpose of Earthing

                         Earthing  of  cables,  equipment,  buildings  and  structures  is  done  for  one  or
                         more of the following purposes:

                        (a) Lightning & surge protection of equipment.

                        (b) Earthing of metal screens of telecommunications cables and equipment for
                            reducing Electromagnetic interference.

                        (c) Human safety.

               19.11.3   Earthing to be provided at

                        (a) The lever frame and other metallic frames of the cabin shall be earthed.

                        (b) The  earthing  shall  be  provided  at  every  location  box  where  cables
                            terminate.

                        (c) The earthing shall be provided at each signal.


                        (d) Wherever possible, the common earthing system to be provided for closely
                            located  location  boxes,  signal  posts,  etc.  Separate  earth  is  required  for
                            equipment requiring functional earth only.