(c) If  DG  Set  is  installed  inside  the  room,  exhaust  pipe  shall  be  extended
                            outside the generator room and the silencer fixed away from the premises.
                            Exhaust pipe shall be appropriately insulated.

                        (d) The starting battery shall be of adequate capacity to meet the starting load.
                            Where  automatic  start  has  been  provided,  the  generator  once  started
                            should stop only with a time delay after main supply is resumed.


                        (e) The  connection  between  the  battery  and  the  DG  Set  shall  be  done  with
                            wires of sufficient cross section to avoid drop in voltage.

                        (f)  The self-starting battery shall normally be on trickle charging mode.


                                     Section 8: Maintenance of Secondary Cells

                16.8.1  (a) Maintenance, testing and repair work on the cells, which may interfere with
                            safe  operation  of  trains  shall  not  be  started  until  movements  are  fully
                            protected.  Temporary  repairs  or  adjustments  shall  be  made  in  such  a
                            manner that safety of train operation is not impaired when repairs and or
                            adjustments  are  made.  Tests  shall be  immediately  carried  out  to ensure
                            that the connected equipment functions satisfactorily.


                        (b) The  battery  room  and  location  boxes  shall  be  kept  well  ventilated,  free
                            from water, oil or dust. Surroundings and batteries shall be kept clean.

                        (c) Connecting cables shall be flexible and sufficiently long, to prevent strain
                            on the battery terminals.


                        (d) The electrical connection shall always be kept tight.

                        (e) The  terminals  and  connections  shall  be  coated  with  pure  vaseline  or
                            petroleum jelly to prevent corrosion. Grease shall not be used.

                        (f)  The Electrolyte shall be maintained at the correct level by topping up as
                            often as necessary with distilled water.


                        (g) Electrolyte  lost  due  to  spillage  shall  be  recouped  with  electrolyte  of  the
                            same specific gravity as that of other cells in the circuit. Electrolyte shall
                            not be added in any other circumstances.

                        (h) Each  cell  shall  be  tested  periodically  and  its  cleaning  and  charging
                            arranged so that its voltage and specific gravity are within specified limits.
                            Test  results  and  dates  of  cleaning  and  charging  adjustments  shall  be
                            recorded on the format enclosed as Annexure:16-MS2, Annexure:16-MS4.
                            A separate card shall be maintained for each battery set. The voltage of
                            individual cell shall not fall below 1.85 Volts.