21.2.2  Fixing in Relay Room

                        As far as practicable, the relay room is not located in the vicinity of chemical
                        factory,  loco  shed  or  engine  ash  pits  etc.  In  case  it  becomes  unavoidable,
                        necessary precautions shall be taken so that relays are least affected by the
                        chemical fumes, dust etc. and are provided with dust free environment. Relay
                        room shall be provided with double locks and door opening shall be monitored
                        through Datalogger.

                         (a) Where  Relays  cannot  be  located  in  the  Cabin,  they  shall  be  housed  in
                            location box of approved type which are properly secured.

                         (b) In 'Q' style relay the code pins configurations for plug in relay shall not be
                            changed  by  drilling  additional  holes  on  plug  board  to  avoid  fixing  of  a
                            wrong relay which may lead to unsafe condition. In Siemen's K-50 relays,
                            the  Code  pins  position  on  base  plate  should  not  be  changed  and  to  be
                            retained as fixed by the manufacturer.

                         (c) All  relay  clips  shall  be  checked  for  proper  locking  in  the  base  when
                            plugged in. Extreme care shall be exercised while removing the clips from
                            the jacks of the plug-in type relay.

                         (d) In  all  installations,  a  relay  index  board  shall  be  provided  for  locating  relays
                            easily.


                         (e) Relays  involving  external  circuits  shall  have  cross  protection  and  double
                            cutting. Signal control relays shall preferably be provided with double cutting.


                         (f)  A contact analysis chart shall be prepared duly showing the contacts used
                            circuit-wise  with  reference  and  spare  contacts  available,  wire  count  for
                            each contact and relay position in the rack.

                         (g) Number of contacts in a circuit shall not exceed 45 Nos. due to voltage
                            drop consideration. The voltage across R1&R2 of a relay shall not be less
                            than 22 V.

                         (h) Where available, spare contacts shall be paralled with working contacts.

                21.2.3  Sealing of Plug-in Relays

                        (a) In  case  of  metal  to  carbon  contact  type  relays,  sealing  shall  be  done  at
                            Manufacturer's premises before dispatch and if the seals have to be broken
                            due to any defect noticed, resealing must be done at the workshops.

                        (b) In case of metal to metal contact type relays, sealing of the cover shall be
                            done by not below the rank of JE (Signal) at site. Whenever seals have to
                            be broken at site for maintenance purposes, the same shall be done by an
                            official not below the rank of JE(Signal).


                        (c) Line  Relays  shall  be  energized  at  the  rated  voltage  specified  in  the
                            specification.